IMCA Safety Flash summarizes key safety matters and incidents
80mm hydrant coupling not compatible with 65mm hose coupling
IMCA has issued new Safety Flash summarizing key safety matters and highlighting lessons learned from maritime incidents.
One case refers to an incident in which replacement fire hydrants were found to be fitted with incorrect coupling sizes, leading to them being incompatible with fire hose couplings. This would have severely impacted the firefighting capabilities of the vessel.
The incident occurred following a number of earlier occasions in the previous five years in which fire hydrant valves in the accommodation had been found leaking. Replacement hydrants were ordered and fitted, but the couplings were found to be incompatible. It was found that the coupling on the hydrant valve in the port side forward thruster room did not fit the adjacent fire hose coupling. The hose coupling measured 65mm and the hydrant coupling measured 80mm.
The investigation revealed the following:
- The hydrant/hose coupling incompatibility was not followed up in a timely manner. Six days elapsed between the discovery of the incompatibility and a Hazard Observation being made;
- A total of thirty hydrant couplings were found with 80mm couplings fitted instead of 65mm couplings. Had there been a fire these thirty couplings (incompatible) on the fire hydrants would not have been serviceable;
- Firefighting capabilities were not entirely restricted as the outside accommodation fire hydrants on each deck were still pressurised and compatible with the fire hoses onboard and the shipboard accommodation sprinkler fire suppression system was available.
The lessons learnt |
|
The fire-fighting equipment should be checked, to carefully and thoroughly inspect all equipment when first received, and to ensure that during fire drills, hoses are properly run and connected to hydrants, including in the accommodation areas.
Source and Image Credit:IMCA