A recent Safety Flash by the International Marine Contractors Association (IMCA), focuses on an incident, in which, a member reports the failure of a 5kg CO2 fire extinguisher during hydrostatic pressure testing, to provide lessons learned.
The incident
The extinguisher, rated to 200bar, was being tested to a pressure of 300bar. The incident occurred when the test pressure reached 196 bar. The extinguisher was 13 years old. No-one was harmed.
What went right?
- The failure occurred under test conditions and no personnel were nearby to get injured;
- The hydrostatic test was a scheduled 5-year test carried out as per the company’s planned maintenance programme.
What went wrong?
- The main body of the extinguisher failed. Our member noted the following points:
- General Wear and Tear: Over time, fire extinguishers are subjected to various environmental factors and conditions that can lead to wear and tear. This wear and tear may include corrosion, stress, or weakening of materials due to exposure to temperature fluctuations and external elements. It is essential to regularly inspect and maintain fire extinguishers to ensure their integrity;
- Age of the Extinguisher: The extinguisher in question was manufactured in July 2010, making it over a decade old at the time of the incident. As fire extinguishers age, their components, including pressure vessels and seals, can deteriorate. Over time, the ability of the extinguisher to withstand high-pressure testing may diminish, increasing the risk of failure.
Lessons learned
- The failure serves as a reminder of the importance of regular inspection, maintenance, and age considerations when dealing with critical safety equipment;
- When in doubt about the condition of a fire extinguisher, consult with experts or manufacturers for guidance on inspection, testing, and replacement intervals;
- IMCA’s member took the following actions:
- Reviewed the current inspection and maintenance program to ensure it is implemented correctly and is rigorous enough for inspection and maintenance of fire extinguishers;
-
- Considered the age of fire extinguishers when planning hydrostatic tests. Older extinguishers may require more frequent testing or replacement to ensure their safety and reliability;
-
- Ensured detailed records of inspections, maintenance, and hydrostatic testing are kept for all fire extinguishers. These records can provide valuable insights into the condition of your equipment over time;
-
- Ensured that personnel involved in handling and testing fire extinguishers are adequately trained and aware of the potential risks associated with aged or damaged equipment.